Structural Retrofitting · Healthcare

ESIC Building, Ezhukone

Kollam

Client type
Central government (CPWD)
Testing
Rebound hammer, UPV
Output
Evaluation report

The project

A structural evaluation of the ESIC Dispensary at Ezhukone, Kollam — a single-storey, load-bearing brick masonry building of about 351 m² (3,777 sq.ft) with RCC lintel bands, verandah columns and roof beams — carried out at the request of CPWD.

What we found

  • Diagonal cracking over wall openings, consistent with settlement of lintel beams, and loss of brick masonry around windows
  • Moisture ingress from the roof and sunshades, with corrosion of lintel-beam reinforcement
  • Rebound hammer readings rated the RCC members 'Fair' to 'Good', but direct-method UPV rated all of them 'Doubtful'
  • A trial pit exposed a sound stepped footing with no signs of settlement
  • Bricks tested at about 8.26 N/mm² (Class 75 to IS 1077), giving a comfortable margin on wall stresses

Recommendations

  • Close and rebuild damaged openings with fresh masonry, with propping during the work
  • Replaster cracked areas with woven glass-fibre fabric reinforcement
  • Provide a sloped sheet roof over the terrace to stop water ingress, and treat corroded reinforcement

Outcome

An evaluation report with distress mapping, NDT and material test results, a masonry stress check and a clear repair methodology for CPWD.