Skip to content
STRUXLABS
← All projects

Structural Retrofitting · Healthcare

Govt. General Hospital — B & C Blocks

Pathanamthitta

Storeys
G+3
Height
26.1 m
Solution
Column jacketing
Testing
UPV, rebound hammer, cores
Loading 3D model…
ETABS 3D MODEL

The project

The B and C blocks of the Government General Hospital, Pathanamthitta — an existing four-storey RCC hospital building with a roof truss — were to be modified to suit proposed architectural changes. Before any change, the structure had to be checked for its capacity.

The challenge

Hospital blocks have to stay in service and carry heavy loads safely. With the proposed changes, several existing columns were found to be over-stressed when the building was analysed with current loads and codes.

Our approach

  • Prepared centre-line plans of every column and beam from the existing drawings
  • Built an ETABS model of the existing structure, including gravity, wind (IS 875 Part 3) and seismic (IS 1893) loads
  • Checked the demand-to-capacity ratio of every column and beam
  • Designed column jacketing for the deficient columns — retrofitted columns cast in M40 concrete with Fe 500 reinforcement and 40 mm cover

Outcome

A retrofitting scheme with column-by-column jacketing details (for example, a 320 × 610 mm column enlarged to 420 × 710 mm), so the blocks can take the proposed changes safely.

The structure in numbers

The ETABS model of this structure has 8 levels and rises 25.1 m over a footprint of about 42 × 42 m. It contains 532 columns and 1903 beams, each checked and designed in the model. Members are designed in M25 and M35 concrete with Fe 500 reinforcement to IS 456: 2000. A modal analysis was run to check how the building sways and vibrates before the members were finalised.

Structural system

Concrete
M25, M35
Reinforcement
Fe 500
Typical columns
320 × 620 mm · 320 × 420 mm · 320 × 610 mm · 370 × 620 mm
Typical beams
200 × 250 mm · 250 × 300 mm · 250 × 400 mm · 250 × 550 mm
Slabs
120 mm thick
Seismic design
IS 1893 (Part 1), zone III, soil type II, special moment-resisting frame
Wind
IS 875 (Part 3), basic wind speed 39 m/s
Analysis
3D ETABS model — linear static analysis
Foundation
Existing foundations retained

Site photos

Govt. General Hospital — B & C Blocks — image 1
Govt. General Hospital — B & C Blocks — image 2