Structural Retrofitting · Healthcare

ESIC Building, Punalur

Kollam

Client type
Central government (CPWD)
Testing
NDT
Output
Evaluation report

The project

A structural evaluation of the ESIC Dispensary at Punalur, Kollam — a single-storey, load-bearing masonry building of about 440 m² (4,735 sq.ft) with consulting rooms, a pharmacy and waiting areas in two wings.

The challenge

Visible damage in an old building does not always mean the structure is unsafe. The question here was whether the cracks and spalling came from a structural problem in the walls and foundations, or from water and corrosion that could be repaired. The answer decides between a targeted repair and a far more expensive strengthening scheme.

What we found

  • No structural cracking in the load-bearing walls; distress was due to moisture ingress and local corrosion
  • A later fin wall without its own foundation had settled and cracked, and was recommended for removal
  • Sunshade slabs showed spalling from reinforcement corrosion, confirmed by UPV grading and elevated half-cell potentials
  • Trial pits at three locations confirmed a sound foundation free of settlement
  • Bricks tested at about 6.98 N/mm² (Class 50 to IS 1077); the masonry stress check showed a comfortable factor of safety

Recommendations

  • Treat wall–slab junction cracks with glass-fibre fabric and replastering
  • Provide a sloped sheet roof over the terrace and a 60 cm PCC plinth protection around the building
  • Repair spalled sunshades and corroded reinforcement

Outcome

A final evaluation report confirming the building is structurally sound, with a targeted repair plan.

Structural system

Foundation
Stepped brick / PCC footing at about 1.5 m depth

Site photos

ESIC Building, Punalur — image 1
ESIC Building, Punalur — image 2
ESIC Building, Punalur — image 3